Construction
Conductor | Solid bare copper (IEC / EN 228, BS 6360, VDE 0295, HD 383) |
Insulation | Fire resistant silicon rubber (HD 22.1, BS 7655 EI 2), colors: BS7671/HD308-S2/VDE0293-308 (for more than 5 cores white core/black numbered) |
Separator | Polyester tape |
Drain Wire | 0.80 mm Solid tinned copper |
Shield | Aluminium laminated polyester tape |
Sheath | HFFR, Red (RAL 3000) EN 50290-2, VDE 0207 HM2, BS 7655 LTS1 / LTS3 |
Technical and Electrical Properties(20°C)
Conductor Resistance (max.) | 1 mm² : 18 Ω/km - 1.5 mm² : 12 Ω/km - 2.5 mm² : 7.4 Ω/km |
Insulation Resistance (min.) | 200 M.Ωxkm |
Operating Voltage | 300 V / 500 V Test Voltage 2000 V |
Temperature Range | Fixed -30 °C ...+90 °C Flexing -5 °C ...+60 °C |
Min. Bending Radius | ixed 8 x Cable Diameter, Flexing 15 x Cable Diameter |
Flame Tests | IEC 60332-1, IEC 60332-3-24, (BS 4066 part 1&3), EN 50266-2-4 |
Insulation Integrity | IEC 60331, BS 6387 C , W, Z, EN 50200 PH30 |
Smoke Density | IEC 61034, BS 7622, HD 606 |
Corrosive Gas Measurement | IEC 60754-2, BS 6425, EN 50267 |